16
POWE RVA LU E 11T G 2
1-3 K VA B/S
—
07
—
07 The line mode
—
4 Operation
4 1 1
Operating modes and strings
Different messages/strings are displayed on
the LCD screen corresponding to different
UPS operating modes, as shown in Table 9.
—
Table 9: Operating modes and strings
Operating mode
Code
No output mode
STbY
Bypass mode
bYPA
Line mode
LINE
Battery mode
bATT
Battery test mode
TEST
ECO mode
ECO
Converter mode
CVCF
4 1 2
Warnings and fault strings
Additionally, different strings, as shown in
Table 10 display with a particular warning or fault.
Only one normal operating string or fault string
is presented at a time. However, if several
warnings happen at the same time, they display
on the LCD alternately. In this case, the normal
operating mode string and the warning string
will be shown alternately. Once a fault occurs,
all previous warnings will not be shown again;
only the fault string will be presented.
—
Table 10: Warning and fault codes
Warning
SITE
Site fail
SITE
Fan fail
FANF
Battery over voltage (over
charged)
HIGH
Battery low
bLOW
Charge fail
CHGF
Inverter temperature high
TEPH
Battery open
bOPN
Overload
OVLD
Digital bigger charger fail
dCHF
Inner temperature high
ITPH
Fault
String
Inverter short
SHOR
Overload fault
OVLD
Inverter soft start fail
ISFT
Bus soft start fail
bSFT
Over temperature fault
OVTP
Inverter Volt Low
INVL
Inverter Volt High
INVH
Bus volt over
bUSH
Bus volt Low
bUSL
Bus short
bUSS
Inverter NTC open
NTCO
Emergency Power Off
EPO
4 1 3
Line mode (LINE)
NOTE
EACH MODE DISPLAYS INFORMATION
ABOUT THE MAINS POWER, THE BATTERY
LEVEL, THE UPS OUTPUT, AND THE
LOAD LEVEL.
The LCD display in Line mode is shown as Figure 7.
The “LINE” string indicates the UPS is working in
Line mode.
—
4 1 Operating modes for all models