25
1 1 T EC H N I C A L SP EC I FI C AT I O N S
—
11 1 Technical Data Sheet
—
11 Technical specifications
GENERAL DATA
G2 1kVA B/ S
G2 2kVA B/ S
G2 3kVA B/ S
Output rated power
900 W
1’800W
2’400W
Output power factor
0.9
0.9
0.9
Topology
Online double conversion
Parallel configuration
No
No
No
Inbuilt batteries
Yes/No
Yes/No
Yes/No
INPUT
Nominal input voltage
220/230/240 VAC
Input voltage tolerance
100-300 VAC (load dependent)
Input current THDi
5% with full resistive load
Frequency range
45-55 Hz / 54-66 Hz
Power factor
≥0.99
OUTPUT
Rated output voltage
220/230/240 VAC
Voltage tolerance
±1% (referred to 230V)
Voltage distortion
<2% linear load, <6% non linear load
Overload capacity (linear
load) on inverter
60s: 106-130% load
10s: 131-150% load
300ms: ≥ 150% load
Nominal frequency
50 or 60 Hz
Crest factor
3:1 (load supported)
EFFICIENCY
Overall system efficiency
Up to 89%
Up to 91%
Up to 91%
In eco-mode
Up to 97.5%
Up to 98%
Up to 98%
ENVIRONMENT
Protection rating
IP20
Storage temperature
UPS: -25°C to 60°C; Batteries: 0°C to 35°C
Operating temperature
0°C to 40°C
Relative humidity
0% to 95%
Altitude (above see level)
1000m without derating
BATTERIES
Type
VRLA (valve regulated lead-acid)
Inbuilt batteries
2x9.4 Ah (B)
4x9.4Ah(B)
6x9.4Ah(B)
Charging current
1.5A/3-6A
adjustable
1.5A/1.5-6A
adjustable
1.5A/1.5-6A
adjustable
Recharge time (inbuilt batteries)
4h to 90%
COMMUNICATIONS
User interface
LCD display
Optional communication cards
SNMP;ModBus;AS400;Environmental monitoring sensor probe
STANDARDS
Safety
IEC/EN 62040-1
EMC
IEC/EN 62040-2
Performance
IEC/EN 62040-3
Manufacturing
ISO 9001:2015, ISO 14001:2015, OHSAS 18001
WEIGHT, DIMENSIONS
Weight
9.2/3.9 Kg
17.4/6.4 Kg
22.7/6.4 Kg
Dimensions w x h x d
144x228x356 mm
102x228x346mm
190x327x399 mm
102x327x390 mm
190x327x399 mm
102x327x390 mm