Navigator 540 | Transmitter |
COM/AWT540/PB–EN Rev. C
45
B.10 Writable floats
Modbus
address
Description
Notes
40000
Chart – Trace 1 – range high
Range from
engineering range low
to engineering range
high. See engineering
range table – Appendix
C, page 52
40002
Chart – Trace 1 – range low
40004
Chart – Trace 2 – range high
40006
Chart – Trace 2 – range low
40008
Chart – Trace 3 – range high
40010
Chart – Trace 3 – range low
40012
Chart – Trace 4 – range high
40014
Chart – Trace 4 – range low
Table B.16: Chart trace range
Modbus
address
Description
Notes
40016
Alarm 1 – Trip point
Range from
engineering range low
to engineering range
high. See engineering
range table – Appendix
C, page 52
40018
Alarm 2 – Trip point
40020
Alarm 3 – Trip point
40022
Alarm 4 – Trip point
40024
Alarm 5 – Trip point
40026
Alarm 6 – Trip point
40028
Alarm 7 – Trip point
40030
Alarm 8 – Trip point
40032
Alarm 1 – Hysteresis
40034
Alarm 2 – Hysteresis
40036
Alarm 3 – Hysteresis
40038
Alarm 4 – Hysteresis
40040
Alarm 5 – Hysteresis
40042
Alarm 6 – Hysteresis
40044
Alarm 7 – Hysteresis
40046
Alarm 8 – Hysteresis
Table B.17: Alarm settings
Modbus
address
Description
Notes
40048
Analog output 1 – Electrical range
high
0 – 22 mA
40050
Analog output 1 – Electrical range low
40052
Analog output 1 – Engineering range
high
Range from
engineering range low
to engineering range
high. See engineering
range table – Appendix
C, page 52
40054
Analog output 1 – Engineering range
low
40056
Analog output 2 – Electrical range
high
0 – 22 mA
40058
Analog output 2 – Electrical range low
40060
Analog output 2 – Engineering range
high
Range from
engineering range low
to engineering range
high. See engineering
range table – Appendix
C, page 52
40062
Analog output 2 – Engineering range
low
40064
Analog output 3 – Electrical range
high
0 – 22 mA
40066
Analog output 3 – Electrical range low
40068
Analog output 3 – Engineering range
high
Range from
engineering range low
to engineering range
high. See engineering
range table – Appendix
C, page 52
40070
Analog output 3 – Engineering range
low
40072
Analog output 4 – Electrical range
high
0 – 22 mA
40074
Analog output 4 – Electrical range low
40076
Analog output 4 – Engineering range
high
Range from
engineering range low
to engineering range
high. See engineering
range table – Appendix
C, page 52
40078
Analog output 4 – Engineering range
low
40080
Analog output 1 – Failure current
0 – 22 mA
40082
Analog output 2 – Failure current
40084
Analog output 3 – Failure current
40086
Analog output 4 – Failure current
Table B.18: Analog output settings