28 OI/JDF200-EN Rev. E
| 2600T Series
10 Hazardous area considerations
11.1.1 10.1.1 Entities
Ex ia IIC Tx Ga
Ex ia IIIC Tx Da IP67
-50°C < Ta < +85°C
Ui= 30 Vdc
Ii= 100 mA
-50°C < Ta < +70°C
Ui= 30 Vdc
Ii= 160 mA
-50°C < Ta < +40°C
Ui= 30 Vdc
Ii= 100 mA
-50°C < Ta < +40°C
Ui= 30 Vdc
Ii= 50 mA
Ex ta IIIC Tx Da IP67*
-50°C < Ta < +85°C
V= 30 Vdc
-50°C < Ta < +70°C
V= 30 Vdc
-50°C < Ta < +40°C
V= 30 Vdc
-50°C < Ta < +40°C
V= 30 Vdc
Ex db IIC Tx Gb
II 2D Ex tb IIIC Tx Db IP67
-50°C < Ta < +75°C
V= 42Vdc
N/A
-50°C < Ta < +75°C
V= 42Vdc
-50°C < Ta < +75°C
V= 42Vdc
Ex nA IIC Tx Gc
Ex tc IIIC Tx Dc IP67
-50°C < Ta < +75°C
V= 42Vdc
-50°C < Ta < +70°C
V= 30Vdc
-50°C < Ta < +40°C
V= 42Vdc
-50°C < Ta < +40°C
V= 42Vdc
Ex ic IIC Tx Gc
-50°C < Ta < +75°C
Ui= 42Vdc
Ii= 100 mA
-50°C < Ta < +70°C
Ui= 30Vdc
Ii= 160 mA
-50°C < Ta < +40°C
Ui= 42Vdc
Ii= 40 mA
-50°C < Ta < +40°C
Ui= 42Vdc
Ii= 40 mA
*The current limitation is applicable only if the equipment is used only with the Ex ta type of protection. See details in the
instruction manual.
Summary of Contents for JDF200
Page 15: ...2600T Series OI JDF200 EN Rev E 15 7 Operation 8 3 1 7 3 1 Easy ...
Page 16: ...16 OI JDF200 EN Rev E 2600T Series 7 Operation ...
Page 17: ...2600T Series OI JDF200 EN Rev E 17 7 Operation ...
Page 18: ...18 OI JDF200 EN Rev E 2600T Series 7 Operation 8 3 2 7 3 2 Device ...
Page 19: ...2600T Series OI JDF200 EN Rev E 19 7 Operation 8 3 3 7 3 3 Process ...
Page 20: ...20 OI JDF200 EN Rev E 2600T Series 7 Operation 8 3 4 7 3 4 8 3 5 7 3 5 Device 8 3 6 7 3 6 ...