![ABB IEC 60870-5-103 Communication Protocol Manual Download Page 56](http://html.mh-extra.com/html/abb/iec-60870-5-103/iec-60870-5-103_communication-protocol-manual_2731056.webp)
4.3
Disturbance recorder file transfer
4.3.1
Disturbance recordings
M17109-111 v9
•
The transfer functionality is based on the Disturbance recorder function. The
analog and binary signals recorded will be reported to the master by polling.
The eight last disturbances that are recorded are available for transfer to the
master. A file that has been transferred and acknowledged by the master
cannot be transferred again.
•
The binary signals that are included in the disturbance recorder are those that
are connected to the disturbance function blocks B1RBDR to B22RBDR.
These function blocks include the function type and the information number
for each signal. For more information on the description of the Disturbance
report in the Technical reference manual. The analog channels, that are
reported, are those connected to the disturbance function blocks A1RADR to
A4RADR. The eight first ones belong to the public range and the remaining
ones to the private range.
4.3.2
Disturbance recordings
M11874-467 v7
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:
•
I
L1
connected to channel 1 on disturbance function block A1RADR
•
I
L2
connected to channel 2 on disturbance function block A1RADR
•
I
L3
connected to channel 3 on disturbance function block A1RADR
•
I
N
connected to channel 4 on disturbance function block A1RADR
•
U
L1E
connected to channel 5 on disturbance function block A1RADR
•
U
L2E
connected to channel 6 on disturbance function block A1RADR
•
U
L3E
connected to channel 7 on disturbance function block A1RADR
•
U
EN
connected to channel 8 on disturbance function block A1RADR
Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.
Binary signals, 128-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
4.3.3
Disturbance Recordings
M17109-141 v8
For each input of the Disturbance recorder function there is a setting for the
information number of the connected signal. The function type and the information
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
50
670 series 2.2 IEC