4.2.6.2
Function block
GUID-031C0F49-BEBD-40FE-A33F-18F1D94BB4B0 v1
I103POSCMDV
BLOCK
POSITION
IEC15000081-2-en.vsdx
IEC15000081 V2 EN-US
Figure 18:
I103POSCMDV function block
4.2.6.3
Signals
PID-6578-INPUTSIGNALS v5
Table 46:
I103POSCMDV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
POSITION
INTEGER
0
Position of controllable object
4.2.6.4
Settings
PID-6578-SETTINGS v6
Table 47:
I103POSCMDV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type
InfNo
160 - 209
-
1
160
Information number for command output
4.2.6.5
Supported information types
IED commands with position for IEC 60870-5-103, I103POSCMDV
GUID-EDA379DC-73E7-48C5-AC3B-A6CA969F351F v2
Number of instances: 50
The function type for each function block instance is selected with the parameter
FunctionType
.
The information number must be selected for the command output.
Table 48:
Each I103POSCMDV has one INF forming one command
INF
Inst 1
Inst 2
Inst 3...
Inst 10
Type
COT
Purpose
Comment
Base
160
161
162
169
1
1,7,9
Position
Current
position
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
49
Communication protocol manual