![ABB IEC 60870-5-103 Communication Protocol Manual Download Page 38](http://html.mh-extra.com/html/abb/iec-60870-5-103/iec-60870-5-103_communication-protocol-manual_2731038.webp)
4.1.5.3
Signals
PID-6864-INPUTSIGNALS v1
Table 16:
I103FLTPROT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting.
64_STL1
BOOLEAN
0
Information number 64, start phase L1
65_STL2
BOOLEAN
0
Information number 65, start phase L2
66_STL3
BOOLEAN
0
Information number 66, start phase L3
67_STIN
BOOLEAN
0
Information number 67, start residual current IN
68_TRGEN
BOOLEAN
0
Information number 68, trip general
69_TRL1
BOOLEAN
0
Information number 69, trip phase L1
70_TRL2
BOOLEAN
0
Information number 70, trip phase L2
71_TRL3
BOOLEAN
0
Information number 71, trip phase L3
72_TRBKUP
BOOLEAN
0
Information number 72, back up trip I>>
73_SCL
REAL
0
Information number 73, fault location in ohm
74_FW
BOOLEAN
0
Information number 74, forward/line
75_REV
BOOLEAN
0
Information number 75, reverse/busbar
76_TRANS
BOOLEAN
0
Information number 76, signal transmitted
77_RECEV
BOOLEAN
0
Information number 77, signal received
78_ZONE1
BOOLEAN
0
Information number 78, zone 1
79_ZONE2
BOOLEAN
0
Information number 79, zone 2
80_ZONE3
BOOLEAN
0
Information number 80, zone 3
81_ZONE4
BOOLEAN
0
Information number 81, zone 4
82_ZONE5
BOOLEAN
0
Information number 82, zone 5
83_ZONE6
BOOLEAN
0
Information number 83, zone 6
84_STGEN
BOOLEAN
0
Information number 84, start general
85_BFP
BOOLEAN
0
Information number 85, breaker failure
86_MTRL1
BOOLEAN
0
Information number 86, trip measuring system
phase L1
87_MTRL2
BOOLEAN
0
Information number 87, trip measuring system
phase L2
88_MTRL3
BOOLEAN
0
Information number 88, trip measuring system
phase L3
89_MTRN
BOOLEAN
0
Information number 89, trip measuring system
neutral N
90_IOC
BOOLEAN
0
Information number 90, over current trip, stage
low
91_IOC
BOOLEAN
0
Information number 91, over current trip, stage
high
92_IEF
BOOLEAN
0
Information number 92, earth-fault trip, stage low
Table continues on next page
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
32
670 series 2.2 IEC
Communication protocol manual