Name
Values (Range)
Unit
Step
Default
Description
MaxIN
1 - 99999
A
1
3000
Maximum residual current IN
MaxUL1
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L1
MaxUL2
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L2
MaxUL3
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L3
MaxUL1-UL2
0.05 - 2000.00
kV
0.05
400.00
Maximum voltage for phase-phase L1-L2
MaxUN
0.05 - 2000.00
kV
0.05
230.00
Maximum residual voltage UN
MaxP
0.00 - 2000.00
MW
0.05
1200.00
Maximum value for active power
MaxQ
0.00 - 2000.00
MVAr
0.05
1200.00
Maximum value for reactive power
MaxF
15.0 - 66.0
Hz
1.0
51.0
Maximum system frequency
4.1.1.5
Supported information types
Measurands in public range, I103MEAS
M11874-385 v8
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
The upper limit is the maximum value that can be encoded into the ASDU
(Application Service Data Unit). Any value higher than this value will be tagged as
OVERFLOW. The factors 1.2 and 2.4 are taken from the 103 standard and require
that a rated value to use as base exists, and then use 1.2 or 2.4 times <rated> as
maxVal
. You can use 2.4 times rated as
maxVal
, but as there is no way to propagate
value to client, the use of a scale factor on <rated> does not make much difference.
You can configure client:
client-scaled-max ::= 1.2 * <rated>
or
client-scaled-max ::= 1.0 * <maxVal>
If the client has a hard-coded gain of 1.2 * <rated> then
client-scaled-
max ::= 1.2 times <maxVal>/1.2
Resolution is <maxVal> / 4095 and hence the lowest possible
maxVal
yields the
best accuracy.
Table 6:
I103MEAS supported indications
INF
Description
148
IL1
144, 145,
146, 148
IL2
148
IL3
147
IN, Neutral current
148
UL1
Table continues on next page
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
25
Communication protocol manual