4.2.1.3
Signals
PID-3969-INPUTSIGNALS v5
Table 28:
I103CMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
PID-3969-OUTPUTSIGNALS v5
Table 29:
I103CMD Output signals
Name
Type
Description
16-AR
BOOLEAN
Information number 16, off/on of autorecloser
17-DIFF
BOOLEAN
Information number 17, block of differential
protection
18-PROT
BOOLEAN
Information number 18, block of protection
4.2.1.4
Settings
PID-3969-SETTINGS v5
Table 30:
I103CMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
4.2.1.5
Supported information types
Function commands in control direction, pre-defined I103CMD
M11874-53 v6
Function command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each output signals.
Table 31:
Pre-defined I103CMD supported indications
INF
Description
16
Auto-recloser on/off
17
Teleprotection on/off
18
Protection on/off
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
41
Communication protocol manual