4.1.4.2
Function block
GUID-25B47484-2976-4063-BD81-AE02D03B08B0 v1
IEC10000290-1-en.vsd
I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290 V1 EN-US
Figure 8:
I103EF function block
4.1.4.3
Signals
PID-3974-INPUTSIGNALS v5
Table 13:
I103EF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
51_EFFW
BOOLEAN
0
Information number 51, earth-fault forward
52_EFREV
BOOLEAN
0
Information number 52, earth-fault reverse
4.1.4.4
Settings
PID-3974-SETTINGS v5
Table 14:
I103EF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
160
Function type (1-255)
4.1.4.5
Supported information types
Earth fault indications in monitor direction, I103EF
M11874-199 v8
Indication block for earth fault in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each output signal.
Table 15:
I103EF supported indications
INF
Description
51
Earth fault forward
52
Earth fault reverse
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
30
670 series 2.2 IEC
Communication protocol manual