![ABB IEC 60870-5-103 Communication Protocol Manual Download Page 50](http://html.mh-extra.com/html/abb/iec-60870-5-103/iec-60870-5-103_communication-protocol-manual_2731050.webp)
PID-3790-OUTPUTSIGNALS v5
Table 37:
I103USRCMD Output signals
Name
Type
Description
OUTPUT1
BOOLEAN
Command output 1
OUTPUT2
BOOLEAN
Command output 2
OUTPUT3
BOOLEAN
Command output 3
OUTPUT4
BOOLEAN
Command output 4
OUTPUT5
BOOLEAN
Command output 5
OUTPUT6
BOOLEAN
Command output 6
OUTPUT7
BOOLEAN
Command output 7
OUTPUT8
BOOLEAN
Command output 8
4.2.3.4
Settings
PID-3790-SETTINGS v5
Table 38:
I103USRCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseMode
Steady
Pulsed
-
-
Pulsed
Pulse mode
PulseLength
0.200 - 60.000
s
0.001
0.400
Pulse length
InfNo_1
1 - 255
-
1
1
Information number for output 1 (1-255)
InfNo_2
1 - 255
-
1
2
Information number for output 2 (1-255)
InfNo_3
1 - 255
-
1
3
Information number for output 3 (1-255)
InfNo_4
1 - 255
-
1
4
Information number for output 4 (1-255)
InfNo_5
1 - 255
-
1
5
Information number for output 5 (1-255)
InfNo_6
1 - 255
-
1
6
Information number for output 6 (1-255)
InfNo_7
1 - 255
-
1
7
Information number for output 7 (1-255)
InfNo_8
1 - 255
-
1
8
Information number for output 8 (1-255)
4.2.3.5
Supported information types
Function commands in control direction, user-defined, I103USRCMD
M11874-72 v6
Function command blocks in control direction with user-defined output signals.
Number of instances: 4
Function type for each function block instance in private range is selected with
parameter
FunctionType
.
Information number must be selected for each output signal. Default values are 1 -
8.
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
44
670 series 2.2 IEC