Description of application and parameters
Application "Enable application"
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
│81
10.20
Application "Enable application"
NOTE
This application can be activated via "Enable device".
If the "Enable application" parameter is set to "activated", the function can temporarily be
blocked via the the 1-bit communication object "Enable".
The function is active if an ON telegram is received on the 1-bit communication object "Enable".
The function is blocked if an OFF telegram is received on the 1-bit communication object
"Enable". This means that no telegram is sent out on the operating mode communication
objects.
10.20.1 General parameters - Enable with
Options:
On telegram
Off telegram
The function is active if an ON telegram is received on the 1-bit communication object "Enable".
The function is blocked if an OFF telegram is received on the 1-bit communication object
"Enable". This means that no telegram is sent out on the operating mode communication
objects.
10.20.2 General parameters - After bus voltage recovery the device is
Options:
Blocked
Enabled
The parameter "After bus voltage recover the device is" exists to permit a defined behaviour at
the "Enable" communication object after a return of bus voltage. Here it is specified whether a
"1" ("enabled") or a "0" ("blocked") is present on the enable object after the return of bus
voltage.
10.20.3 General parameters — Use of automatic enable/blockage
Options:
No
Automatic enable
Automatic blockage
Automatic enable or automatic blockage can be activated via parameter "Use of automatic
enable/blockage". It can also be used to deactivate an automatic function.