Description of application and parameters
Application "1-button step switch"
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
│49
10.9.3 Extended parameters - Time for long operation
Options:
00.300 ... 02.500
A differentiation can be made between a short or long operation of the button. With a short
operation of the button, the next level forward is switched to in each case. With a long
operation, the first level is activated. Thus with a long button press a jump back from every
position to the first level is possible, without having to run through the remaining levels.
Via the "Duration of long operation", the time is specified from which a long button press is
recognised and the object values are reset. The first level must be set again with a press of the
button. Any time from 0.3 to 2.5 seconds can be set. A typical value after which a jump-back to
level 1 is made is 0.4 s.
10.9.4 Extended parameters — Sending of objects
Options:
For change of value
For operation
The parameter "Sending of objects" specifies whether the object values for every button
operation are sent out or only if the object values have changed since the last sending out.
10.9.5 Extended parameters - Object values
Options:
Normal
Inverse
The object values can be sent "normal" or "inverse" via their associated 1-bit communication
objects. If the parameter "Object values" is set to "inverse" then all 1-bit communication objects
of the individual levels send out their values inverted.
10.9.6 Extended parameters - Bit pattern of object values
Options:
x of n
1 of n
The levels can be switched in two different bit patterns:
x of n (for 5 objects, object 0 to 4)
1 of n (for 5 objects, object 0 to 4)
00000
10000
11000
11100
11110
11111
00000
10000
01000
00100
00010
00001