Installation and maintenance guide
1ZSC000563-AAX EN, REV. A, 2019-03-21
43
Nominal capacitance
The capacitance (C
2
) depends on the transformer, and it is not possible to give a nominal value that is valid
for all service conditions. Thus, it is important to measure and record the capacitance (C
2
) for future
reference, such as repairs, service etc.
Type
Space for CT = 600 mm
C
1
C
2
(test tap)
GSC 200
617
<5000
GSC 300
632
<5000
GSC 300E
821
<5000
GSC 400
612
<5000
GSC 450S
648
<5000
GSC 450E
850
<5000
GSC 500
799
<5000
GSC 500E
915
<5000
Procedure
1.
De-energize the transformer.
2.
Disconnect the external connections from the outer terminal of the bushing.
3.
Remove the cover (2).
Part
Article number
Cover
2769 522-M
O-ring
1ZSC00442-CAK
G004942
4.
Connect the measuring equipment.
1.
Connect the low voltage cable to the stud (1).
2.
Connect the high voltage cable to the outer
terminal.
3.
Connect the ground cable to the bushing
flange.
G004944