30
Installation and maintenance guide
1ZSC000563-AAX EN, REV. A, 2019-03-21
2.
Remove the M16 nut (10).
G000238
3.
Carefully clean the bottom end of the bushing, and the inside of the center hole. Look for damage.
4.
Pull down the uper draw rod (1) from the bottom end of the bushing.
5.
Remove the transport cover (13) from the
transformer (11) and the lower draw rod (4).
G004219
6.
Only for the GSC 200/300/300E/400/450S. Make
sure the compensating device (14) is still in the
bushing.
G004224
7.
Lift the bushing to a position above the installation opening on the transformer.
CAUTION!
Make sure that there are installation markings on the bushing flange. The bushing must
always be installed in the same direction on the transformer.