L2234
Emax
72/158
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000460R0002
L2778
Alarm message
Description
Notes
Harmonic dist.
Harmonic distortion alarm
Busbar currents with form factor > 2.1
Contact wear
Alarm for contact wear
Contact wear = 100%
G (TRIP OFF)
Alarm for protection G
Gext (TRIP OFF)
Alarm for protection Gext
T Alarm
Alarm for protection T
Temperature outside range
T (TRIP OFF)
Alarm for protection T
U Alarm
Alarm for protection U
UV Alarm
Alarm for protection UV
OV Alarm
Alarm for protection OV
RV Alarm
Alarm for protection RV
RP Alarm
Alarm for protection RP
UF Alarm
Alarm for protection UF
OF Alarm
Alarm for protection OF
LC1 Load
Alarm for load control LC1
LC2 Load
Alarm for load control LC2
L1 Sensor
Alarm for L1 phase current sensor
Phase L1 sensor disconnected or faulty
L2 Sensor
Alarm for L2 phase current sensor
Phase L2 sensor disconnected or faulty
L3 Sensor
Alarm for L3 phase current sensor
Phase L3 sensor disconnected or faulty
Ne Sensor
Alarm for Ne phase current sensor
Phase Ne sensor disconnected or faulty
Gext Sensor
Alarm for Gext current sensor
Gext sensor disconnected or faulty
Warning signal
Protection in alarm, with no trip (trip=off)
TC disconnected
Trip Coil disconnected or faulty
Rating Plug
Rating Plug Error absent or faulty
Power factor
Alarm for power factor
The power factor module is lower than the specified threshold
Phase cycle
Phase cycle inverted
Invalid date
Clock information lost
CB status
CB state error
Probable error in Q26 and/or Q27
Installation
Key Plug Error
CB not defined
State of circuitbreaker inconsistent (Open/Closed)
Probable error in Q26 and/or Q27
Local Bus
Local Bus error
See par. 13.7
Contact wear
Contact wear prealarm
Contact wear
≥
80%
L prealarm
Protection L prealarm
T prealarm
Protection T prealarm
Frequency range
Frequency out of range
Warning Iw
Iw threshold exceeded
Timing L
Timing protection L
Timing S
Timing protection S
Timing G
Timing protection G
Timing Gext
Timing protection local Gext
Timing U
Timing protection U
13.6.3 Table of error and warning messages
All the messages which can be shown on the display relating to incorrect configurations, generic alarms or deriving from the protection functions
and linked to useful information are described below.
The following symbols in the warning signals have the following meanings:
= Warning signal / Protection in alarm mode, with no trip (trip=off).
= Protection in alarm mode, with trip at end of delay (trip=on).
= Information, no action, excepting displaying by the relay.