Page 140
© Copyright 2021 ABB. All rights reserved.
Table 12
-
B: Connector J3 Pin Definitions
Pin
Name
Definition
Comments/Connections
8
VPWR
-
V(
-
) Power
Power for ES772A, connect to VBus(
-
)
9
STATUS1_RTN
Reference for STATUS1
Connect to C pin of micro switch of Contactor 1.
10
STATUS1
Contactor 1 Status Monitor
Connect to NO pin of micro switch of Contactor 1.
11
SHUNT+
Positive Battery Shunt
Input
Polarity is during battery discharge
12
LVD1_COIL
Contactor 1 coil input
Connect to one side of Contactor 1 coil,
13
DIST_ALM_2
Trip
-
Indicator Input
-
2 for US Style CB or
GMT Fuse. Alarm on closure to VBus(
-
).
Connect to NC terminal of breaker micro switch or to
indicator lead of GMT fuse, other end (C) referenced to
VBus(
-
).
14
EXT BAT SW2
Alarm input for external battery
disconnect switch; alarms on closure to
VBus(
-
).
Connect to NC micro switch of US Style CB, other end (C)
referenced to VBus(
-
), micro switch must close upon
manual opening of CB.
Table 12
-
A: Connector J1 Pin
-
out Definitions (continued)
Pin
Name
Definition
Comments
1
BATT2_SENSE
Polarity Sense for String 2.
Connect to battery negative VBus(
-
) of string 2.
2
STATUS2_RTN
Reference for STATUS 2.
Connect to C pin of micro switch of Contactor 2.
3
STATUS2
Contactor 2 Status Monitor.
Connect to NO pin of micro switch of Contactor 2.
4
LVD2_COIL
Contactor 2 coil input.
Connect to one side of Contactor 2 coil, other side of coil
connected to VBus(+).
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...