Installation Category
CPS6000 is suitable for connection to ac utility systems where the expected level of lightning surges
complies with ANSI C62.41 Category B or IEC 60664
-
1 Overvoltage Category II.
A service entrance surge protector is required in applications where the installation categories can not
be classified as being compliant to either ANSI C62.41 Category B or IEC 60664
-
1 Overvoltage Category
II.
CPS6000 rectifiers have been tested for repeated lightning surges typically found in an Overvoltage
Category III installation; however, a service entrance surge protector is recommended in cabinet
applications to bring the power feeds in compliance to the installation categories above. The service
entrance protection should be coordinated with the protection provided in the power modules.
The power module provides common
-
mode protection via a 320V MOV in series with a 2500V
gas
-
discharge device and differential
-
mode protection via a 320V MOV in series with a 3.5A fuse.
Rectifiers are individually UL Recognized (UL1950), cUL
Certified (CSA 22.2 234) or evaluated to EN60950 by an EC
Notified Body, as appropriate.
European Economic Community (EEC) Directives
EMC Directive 89/336/EEC
Low Voltage Directive 73/23/EEC as amended by Marking
Directive 93/68/EEC
Note 1
:
CPS6000 can be used with four strings of batteries depending on Distribution Module
Note 2
:
When used with Single
-
Slot and Double
-
Slot Distribution Modules, maximum output is limited to 200A or the size of
the LVD contactor installed (if smaller). See Section 3 for limitations on maximum currents through Distribution
Modules.
Note 3
:
Operating temperatures and required airflow are different when used with specific rectifiers. See Tables 2
-
D through
2
-
F for rectifier information.
Note 4
:
For altitudes above 5000 feet, derate the temperature by 3.6 °F per 1000 feet. For altitudes above 1524 meters,
derate the temperature by 0.656 degrees Celsius per 100 meters.
Note 5
:
Power Unit Install Positions:
•
Install these units in order beginning with the right most Power Slot
First:
Distribution Module
Second:
Ringer Chassis
•
Install these units in order beginning with the left most Power Slot
First:
Rectifiers
Table 2
-
A: CPS6000 System Specifications (continued)
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...