Step
Action
3.
The
Float Settings
option will be highlighted, press the
Display Menu
key to access the Float Settings
Menu.
4.
The
Set Point
option will be highlighted. Press the
Display Menu
key to view or change the Float voltage
Set Point. Use the left and right arrow keys to adjust the
Set Point
voltage. Once the Voltage has been
set to the desired value Press the
Display Menu
key to save the change. The voltage range is
42.0 to 56.5 Volts. Factory default is
-
54.5V.
5.
Select Voltage Alarms to set the four Voltage Alarm thresholds.
Alarm
Description
Very High Voltage
Major
Alarm occurs and the unit is shut down when the system detects voltage above its set
threshold. The threshold can be set from 50V to 60V in 1V increments. The factory default
setting is 57V
High Voltage
Minor
Alarm indicates an abnormally high output voltage but does not shut the unit down. The
alarm threshold can be set from 50V to 60V in 1V increments. The factory default setting
is 56V.
BD (Battery on Discharge)
Major
Alarm occurs when the system is operating either completely or partially on battery pow-
er. The alarm threshold can be set from 46V to 55V in 0.1V increments. The factory default
setting is 51.0V.
Very Low Voltage
Major
Alarm indicates an imminent system shutdown due to discharging batteries or low output
voltage. Factory default
-
46.0V.
Note: Factory defaults listed are for the standard QS840A controller.
Status
This area of the menu provides an overview of system threshold settings, equipment operation, and
present component values. Only state type information is available in this menu. No configuration or
operations are possible from the Status portion of the menu system. Following are the elements
available in the Status menu.
Rectifiers:
Total installed capacity of the system, total output current of all rectifiers, and the
individual rectifier currents by rectifier number (Gnn).
Batteries:
The following battery management information is available under Status:
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...