74
CoriolisMaster FCB400, FCH400
CORIOLIS MASS FLOWMETER | CI/FCB400/FCH400-EN REV. H
… 7 Commissioning
… Parameterization of the device
AssetVision Basic with the ABB CoriolisMaster Device Type
Manager (DTM)
The required software and drivers can be downloaded
using the adjacent download link.
Installation of the software and connection to the flowmeter:
1.
Unpack the downloaded archive file to the c:\temp folder.
2.
AssetVision Basic (DAT200) install
‘3KXD151200S0050_Tool_DAT200_Asset_Vision_Basic’.
3.
HART Communication DTM install
‘ABB DTM HART Communication ServicePort’.
4.
CoriolisMaster DTM FCXxxx install
‘3KXF410100S0002_DTM_FCXxxx_HART_CoriolisMaster‘.
5.
Connect the flowmeter with the PC / laptop, see chapter
Parameterization via the infrared service port adapter
on
page 75 or
Parameterization via HART®
on page 76.
6.
Power-up the power supply for the flowmeter and start
AssetVision Basic on the PC / laptop
• Select HART and ‘ABB HART Communication ServicePort’.
• Select the corresponding COM port.
• Baud
rate
19200.
• The flowmeter is detected and the CoriolisMaster DTM
starts automatically.
• Confirm the dialog field ‘Upload parameters’ by selecting
‘yes’.
Field Information Manager (FIM) with the ABB
CoriolisMaster Field Device Information Package
Download the ABB Field Information Manager (FIM) using
the adjacent download link.
Download the ABB FDI package using the adjacent
download link.
Installation of the software and connection to the flowmeter:
1.
Install ABB Field Information Manager (FIM).
2.
Unpack the ABB FDI package into the c:\temp folder.
3.
Connect the flowmeter with the PC / laptop, see chapter
Parameterization via the infrared service port adapter
on
page 75 or
Parameterization via HART®
on page 76.
4.
Power-up the power supply for the flowmeter and start the
ABB Field Information Manager (FIM).
5.
Drag and drop the ‘ABB.FCXxxx.01.00.00.HART.fdix’ file to the
ABB Field Information Manager (FIM). No special view is
needed for this.
6.
Right-click
1
as shown in Figure 66.
Figure 66: Select FIM – ‘Device Settings’
7.
Select ‘DEVICE SETTINGS’
2
as shown in Figure 66.