64
CoriolisMaster FCB400, FCH400
CORIOLIS MASS FLOWMETER | CI/FCB400/FCH400-EN REV. H
… 6 Electrical connections
… Digital communication
Two port connection without power over Ethernet
Terminal designation:
Port Pin Function
Color
coding
1
Pin 1
RD+
White / Orange
Pin 2
RD
−
Orange
Pin 3
TD+
White / Green
Pin 4
TD
−
Green
2
Pin 1
RD+
White / Orange
Pin 2
RD
−
Orange
Pin 3
TD+
White / Green
Pin 4
TD
−
Green
Ethernet communication
Equipped with an Ethernet Card, CoriolisMaster provides 2
Ethernet Ports supporting a Ring, Star and Daisy Chain Network
configuration.
In addition to the Ethernet Card, a plug-in Card providing ‚Power
over Ethernet‘ is available. This Card allows to power the 24 V DC
Version of the flowmeter through Ethernet without the need for
additional power supply.
EtherNet/IP™ protocol
Note
The EtherNet/IP protocol is not secure, as such. The application
should be assessed before Implementation to ensure the
protocol is suitable.
With implemented CoriolisMaster EtherNet/IP protocol, cyclic
Communication is supported. Process Variables, Diagnostic
Data and Device Status Information can be accessed cyclically.
For Device Configuration a Webserver is available providing
full access to all parameter and diagnostic data.
EtherNet/IP Interface
Configuration
Through the Webserver or the local operating
Interface (Display).
EtherNet / IP ProductCode 5001
EDS file
FCB4_FCH4_01_01.eds
Device profile
Profile 0x43, Generic Device, (keyable).
Supporte standards and
protocols
Common Industrial Protocol (CIP™) Vol1, Ed 3.25
EtherNet/IP™ Adaptation of CIP™, Vol2, Ed 1.23
Cable Cat
5
Further Ethernet communication protocols
Note
The device supports following security modes:
Secured Protocols:
Webserver https:
Security modes
Used ports by Webserver: TCP 443
Security is based on .x509 Certificates
Protocol could be deactivated via HMI.
Unsecured protocols:
EtherNet / IP and Modbus TCP
Used ports by EtherNet/IP: TCP 44818, UDP 2222
Used ports by Modbus/TCP: TCP 502
All protocols can be enabled / disabled in the HMI
Menu.Ethernet
Note
For EMC reasons, if an Ethernet output and a current or digital
output are used simultaneously, a shielded cable must also be
used for the current or digital output. The shield of the cable
must be connected in the unit., see
Connection to integral
mount design
on page 56 and
Connection to remote mount
design
on page 58.