45
Active
Inactive
Function 2
Function 1
Active
Inactive
Function
SEt UP
dIGtAL
SELECt
CtrL 2
CtrL 1
NONE
AM Src
2nd-2
NONE
MAN.Src
2nd-2
NONE
C-OUt
---
AUt.SrC
2nd-2
NONE
Page header – Set Up Digital.
To advance to
Control Configuration Level
frame press the
switch.
Select Controller
Select the controller to be programmed (1 or 2).
✶
Note. In the remaining frames press the
switch to view the controller selected.
Auto/Manual Control Mode Source
Select a source to switch between Auto and Manual control modes. When Manual control mode
is selected, the output reverts automatically to the value set in the
Configured Output
frame (see
below).
Manual
Active
Inactive
Auto
Manual Control Mode Source
Select a source to switch to Manual control mode. When manual control mode is selected, the
output reverts automatically to the value set in the
Configured Output
frame (see below).
Manual
Active
Inactive
Configured Output
Set the control output value required when Manual control mode is selected.
Auto Control Mode Source
Select a source to switch to Auto control mode.
Auto
Active
Inactive
Continued on next page.
4
CONTROL CONFIGURATION LEVEL…
4.5
Set Up Digital Page
Information.
• Digitally selectable control modes and set point types.
• Up to 3 digitally selectable local set points.
• Digital signal sources – can be from external digital inputs, internal alarms, logic equations, control modes, ramp/soak
events or totalizer signals.
Note.
• The complete list of digital sources is shown in Table 3.1 on page 17.
• Digital sources can be either leading edge triggered or level triggered, depending on the parameter function (single or
dual).
Single function parameters
, e.g. set point 1 selection, are
leading edge triggered
,
i.e. the active logic state can be removed after the function is selected.
Dual function parameters
, e.g. auto/manual control mode selection, are
level triggered
,
i.e. the active logic state must be maintained to select the alternative function.