Default Action (Process Variable)
Select the default control action required if the process variable exceeds its fault detection level
(set in the
Set Up Input
page,
BASIC CONFIGURATION LEVEL
):
dEF–OP
–
revert to manual control mode and change the control output to the
Default Output
value (see next frame).
HOLd
–
revert to manual control mode and hold the output at its current value.
NONE
–
no action.
Default Output
Set the default control output value used if the process variable exceeds the fault detection level
(between 0 and 100% in 1 % increments).
✶
Note. For boundless motorized valve control, the default output setting can only be 0
or
100%.
Default Action (Set Point)
Select the default control action required if the remote set point exceeds its fault detection level
(set in the
Set Up Input Page
,
BASIC CONFIGURATION LEVEL
):
dEF–SP
–
revert to local set point and use the
Default Set Point
value (see next frame).
LOCAL
–
revert to local set point.
NONE
–
no action.
Default Set Point
Set the default control set point value used if the remote set point exceeds the fault detection
level (in engineering units).
Default Action (Position Feedback)
Select the default control action required if the position feedback exceeds its fault detection level
(set in the
Set Up Input Page
,
BASIC CONFIGURATION LEVEL
):
HOLd
–
revert to manual control mode and hold the valve at its current position.
NONE
–
no action.
Return to
Select Controller
frame.
dFA-PV
dEF-OP
HOLd
NONE
SELECt
dEF-OP
----
------
dFA-SP
dEF-OP
LOCAL
NONE
dEF-SP
----
dFA-Fb
HOLd
NONE
rSP–x
enabled
rSP–x
not enabled –
Input Assignment
Page
bNdLSS
Ht-CL
Std
P-PrOP
C-tYPE
C-tYPE
4
CONTROL CONFIGURATION LEVEL…
…4.3.5
Set Up Control Page (default control actions)