![ABB COMMANDER 1900 Series Programming Manual Download Page 46](http://html.mh-extra.com/html/abb/commander-1900-series/commander-1900-series_programming-manual_267046.webp)
44
4.4
Set Up Operating Page
Information.
• Customized display of parameters in the Operating Page.
• Power-fail indication – if enabled,
LINE FAILEd
is displayed to indicate that a power failure has occurred.
• Auto/Manual switch
– enable or disable.
YES
NO
SEt UP
OP PGE
SELECt
CtrL 2
CtrL 1
NONE
PF-INd
Aut.MAN
ENbL-Y
ENBL-N
Mr AdJ
YES
NO
SP-SEL
YES
NO
SP-AdJ
YES
NO
r-AdJ
YES
NO
b-AdJ
YES
NO
SELECt
------
INCMNt
--
CtrL 2
CtrL 1
Page header – Set Up Operating Page.
To advance to
Set Up Digital Page
press the
switch.
Select Controller
Select the controller to be programmed (1 or 2).
✶
Note. In the remaining frames press the
switch to view the controller selected.
Bargraph Increment
The deviation from set point is shown on the bargraph on the faceplate.
Set the percentage deviation represented by each bar, between 1 and 10% in 1% increments.
Power Fail Indication Enable
Enable or disable power failure indication:
YES
–
enable
NO
–
disable
Auto/Manual Select Enable
Enable or disable the
switch on the faceplate:
ENbL-Y
–
enable
ENbL-N
–
disable
Manual Reset Adjustment Enable
Enable or disable display and adjustment of the
Manual Reset
frame in the
Operating Page
:
YES
–
enable
NO
–
disable
Set Point Select Enable
Enable or disable adjustment of the
Set Point Type Selection
frame in the
Operating Page
:
YES
–
enable
NO
–
disable
Set Point Adjust Enable
Enable or disable adjustment of the
Control Set Point
value in the
Operating Page
:
YES
–
enable
NO
–
disable
Remote (or Cascade) Set Point Ratio Adjust Enable
Enable or disable display and adjustment of the
Remote (or Cascade) Set Point Ratio
in the
Operating Page
.
YES
–
enable
NO
–
disable
Remote (or Cascade) Set Point Bias Adjust Enable
Enable or disable display and adjustment of the
Remote (or Cascade) Set Point Bias
in the
Operating Page
.
YES
–
enable
NO
–
disable
Return to
Select Controller
frame.