15
3.5
Set Up Relay Output
Information.
• Relays – can be energized by alarms, logic equation results, digital inputs, control and set point modes, real time events,
(timer option), totalizer wrap signal (totaliser option) and ramp/soak programs/segments (profile option).
• External Totalizer count function – external counter can only be driven by relays fitted on module type 3 (4 relay module)
in module positions 3, 4 and 5.
• Polarity – to allow failsafe settings.
• Control outputs – time proportioning (on type 1 and 2 modules or the first 2 relays only on type 3 module), valve open/
close or on/off control.
Alarm Acknowledge
Profile Segment 0
Profile Segment 99
Valve Control
Control Output
Control States
Control Mode
Local Set Point
2nd Set Point
Timer
Logic Equation 1
Logic Equation 8
Digital Input 1
Digital Input 2
Alarm A1
Alarm D4
Relay Source
Select Relay Output
Polarity Selection
Relay 5.1
Relay 5.2
Relay 5.3
Relay 5.4
Module Position
Relay No.
Alarm A1
Active
Energized
Positive
Alarm A1
Active
De-energized
Negative
Alarm A1
Inactive
Positive
Alarm A1
Inactive
Energized
Negative
De-energized
Relay Contacts
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
Source State
Polarity
Relay State
3
BASIC CONFIGURATION LEVEL…