Technical data
71
Technical data
What this chapter contains
This chapter contains the technical specifications of the drive, e.g. the ratings, sizes
and technical requirements, and provisions for fulfilling the requirements for CE and
other markings.
Ratings
The nominal current ratings for the ACSM1-04 with 400 V AC supply are given
below.
Drive type
ACSM1-04xx…
Frame
size
Input ratings
Output ratings
I
1N
*I
1N
I
2N
I
2cont4k
I
2cont8k
I
2cont16k
I
2max
P
N
A
A
A
A
A
A
A
kW
HP
-02A5-4
A
1.9
3.2
2.5
3.0
2.5
2.0
5.3
0.75
1
-03A0-4
A
2.6
4.7
3.0
3.6
3.0
2.2
6.3
1.1
1.5
-04A0-4
A
3.3
5.7
4.0
4.8
4.0
2.4
8.4
1.5
2
-05A0-4
A
4.6
7.8
5.0
6.0
5.0
2.5
10.5
2.2
3
-07A0-4
A
5.8
9.8
7.0
8.0
5.5
3.0
14.7
3
3
-09A5-4
B
7.9
12
9.5
10.5
9.5
5.0
16.6
4
5
-012A-4
B
10
15
12
14
12
6.0
21
5.5
7.5
-016A-4
B
14
20
16
18
13
7.5
28
7.5
10
-024A-4
C
20
21
24
27
24
18
42
11
15
-031A-4
C
27
26
31
35
31
20
54
15
20
-040A-4
C
33
29
40
44
35
22
70
18.5
25
-046A-4
C
39
35
46
50
38
24
80
22
30
-060A-4
D
55
45
60
65
55
28
105
30
40
-073A-4
D
65
51
73
80
60
31
128
37
50
-090A-4
D
78
58
90
93
65
34
150
45
60
*Without mains choke
PDM-00425726
I
1N
Nominal input current (rms) at 40 °C (104 °F).
I
2N
Nominal output current at 40 °C (104 °F).
I
2contxk
Continuous output current at a switching frequency of 4/8/16 kHz at 40 °C (104 °F).
P
N
Typical motor power.
I
2max
Maximum short-time output current. See section
below.
Note:
Frame sizes C and D can be used continuously without a mains choke at up to 50% of nominal
shaft power (i.e. at continuous nominal torque up to 50% of rated speed).
To achieve the rated motor power given in the table, the rated current of the drive must be higher than
or equal to the rated motor current.
The DriveSize dimensioning tool available from ABB is recommended for selecting the drive, motor
and gear combination for the required motion profile.
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 0 75 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 24: ...The ACSM1 04 24...
Page 30: ...Planning the cabinet assembly 30...
Page 46: ...Planning the electrical installation 46...
Page 70: ...Maintenance 70...
Page 84: ...Technical data 84...
Page 90: ...Mains filters 90...
Page 96: ...Dimension drawings 96 Frame size A...
Page 97: ...Dimension drawings 97...
Page 98: ...Dimension drawings 98 Frame size B...
Page 99: ...Dimension drawings 99...
Page 100: ...Dimension drawings 100 Frame size C air cooled module...
Page 101: ...Dimension drawings 101...
Page 102: ...Dimension drawings 102 Frame size C for cold plate mounting...
Page 103: ...Dimension drawings 103 Frame size D air cooled module...
Page 104: ...Dimension drawings 104 Frame size D for cold plate mounting...
Page 106: ...Dimension drawings 106 Mains filters type JFI xx...
Page 108: ...Dimension drawings 108 Braking resistors type JBR xx...
Page 110: ...Dimension drawings 110...
Page 111: ......