Technical data
76
AC input (supply) connection
Voltage (
U
1
)
380 … 480 V AC +10%/-15%, 3-phase
Frequency
50 … 60 Hz ±5%
Network type
Grounded (TN, TT) or ungrounded (IT).
Note:
Connection to an ungrounded (IT) or corner-grounded delta network is not allowed
at altitudes of 2000 m (6600 ft) or higher.
Imbalance
Max.
±3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Terminals
Frame A: Detachable screw terminal block for 0.25 … 4 mm
2
wire.
Frame B: Detachable screw terminal block for 0.5 … 6 mm
2
wire.
Frames C and D: Screw lugs for 6…70 mm
2
wire included. Suitable crimp lugs can be
used instead.
DC connection
Voltage
436 … 712 V DC
Ratings
Terminals
Frame A: Detachable screw terminal block for 0.25 … 4 mm
2
wire.
Frame B: Detachable screw terminal block for 0.5 … 6 mm
2
wire.
Frames C and D: Screw lugs for 6…70 mm
2
wire included. Suitable crimp lugs can be
used instead.
Motor connection
Motor types
Asynchronous induction motors, asynchronous servo motors, synchronous permanent
magnet motors
Frequency
0 … 500 Hz
Current
See section
Switching frequency
Selectable between 2 … 16 kHz. Default: 4 kHz, above which output current derated
Maximum motor cable
length
50 m (164 ft) with screened cable
75 m (246 ft) with unscreened cable
Drive type
ACSM1-04xx…
I
dcN
C
(A)
(µF)
-02A5-4
3.3
120
-03A0-4
3.9
120
-04A0-4
4.8
240
-05A0-4
6.5
240
-07A0-4
8.7
240
-09A5-4
12
370
-012A-4
15
740
-016A-4
20
740
-024A-4
29
670
-031A-4
38
670
-040A-4
44
1000
-046A-4
54
1000
-060A-4
73
1340
-073A-4
85
2000
-090A-4
98
2000
I
dcN
Average DC input current requirement when running a typical induction motor
at
P
N
at a DC link voltage of 540 V (which corresponds to an AC input voltage
of 400 V).
C
Capacitance of DC link.
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 0 75 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 24: ...The ACSM1 04 24...
Page 30: ...Planning the cabinet assembly 30...
Page 46: ...Planning the electrical installation 46...
Page 70: ...Maintenance 70...
Page 84: ...Technical data 84...
Page 90: ...Mains filters 90...
Page 96: ...Dimension drawings 96 Frame size A...
Page 97: ...Dimension drawings 97...
Page 98: ...Dimension drawings 98 Frame size B...
Page 99: ...Dimension drawings 99...
Page 100: ...Dimension drawings 100 Frame size C air cooled module...
Page 101: ...Dimension drawings 101...
Page 102: ...Dimension drawings 102 Frame size C for cold plate mounting...
Page 103: ...Dimension drawings 103 Frame size D air cooled module...
Page 104: ...Dimension drawings 104 Frame size D for cold plate mounting...
Page 106: ...Dimension drawings 106 Mains filters type JFI xx...
Page 108: ...Dimension drawings 108 Braking resistors type JBR xx...
Page 110: ...Dimension drawings 110...
Page 111: ......