Maintenance
66
Cooling fan
The actual lifespan of the cooling fan depends on the drive usage and ambient
temperature. Fan failure can be predicted by the increasing noise from fan bearings
and the gradual rise in the heatsink temperature in spite of heatsink cleaning. If the
drive is operated in a critical part of a process, fan replacement is recommended
once these symptoms start appearing. Replacement fans are available from ABB.
Do not use other than ABB-specified spare parts.
Fan replacement (Frames A and B)
Detach the power cable clamp plate and terminal blocks. Release the retaining clips
(arrowed) carefully using a screwdriver. Pull the fan holder out. Disconnect the fan
cable. Carefully bend the clips on the fan holder to free the fan.
Install new fan in reverse order.
Note
: The airflow direction is bottom-to-top. Install the fan so that the airflow arrow
points up.
Airflow direction
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 0 75 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 24: ...The ACSM1 04 24...
Page 30: ...Planning the cabinet assembly 30...
Page 46: ...Planning the electrical installation 46...
Page 70: ...Maintenance 70...
Page 84: ...Technical data 84...
Page 90: ...Mains filters 90...
Page 96: ...Dimension drawings 96 Frame size A...
Page 97: ...Dimension drawings 97...
Page 98: ...Dimension drawings 98 Frame size B...
Page 99: ...Dimension drawings 99...
Page 100: ...Dimension drawings 100 Frame size C air cooled module...
Page 101: ...Dimension drawings 101...
Page 102: ...Dimension drawings 102 Frame size C for cold plate mounting...
Page 103: ...Dimension drawings 103 Frame size D air cooled module...
Page 104: ...Dimension drawings 104 Frame size D for cold plate mounting...
Page 106: ...Dimension drawings 106 Mains filters type JFI xx...
Page 108: ...Dimension drawings 108 Braking resistors type JBR xx...
Page 110: ...Dimension drawings 110...
Page 111: ......