47
Electrical installation
What this chapter contains
This chapter describes the electrical installation procedure of the drive.
WARNING!
The work described in this chapter may only be carried out by a qualified
on the first pages of this manual. Ignoring
the safety instructions can cause injury or death.
Make sure that the drive is disconnected from the supply (input power) during
installation. If the drive is already connected to the supply, wait for 5 minutes
after disconnecting the input power.
Checking the insulation of the assembly
Drive
Do not make any voltage tolerance or insulation resistance tests (e.g. hi-pot or
megger) on any part of the drive as testing can damage the drive. Every drive has
been tested for insulation between the main circuit and the chassis at the factory.
Also, there are voltage-limiting circuits inside the drive which cut down the testing
voltage automatically.
Supply cable
Check the insulation of the supply (input) cable according to local regulations before
connecting to the drive.
Motor and motor cable
Check the insulation of the motor and motor cable as follows:
1. Check that the motor cable is connected to the motor, and disconnected from the
drive output terminals U2, V2 and W2.
2. Measure the insulation resistance between each phase and the motor PE
conductor by using a measuring voltage of 1 kV DC. The insulation resistance
must be higher than 1 Mohm.
ohm
M
3~
U1
V1
W1 PE
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 0 75 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 24: ...The ACSM1 04 24...
Page 30: ...Planning the cabinet assembly 30...
Page 46: ...Planning the electrical installation 46...
Page 70: ...Maintenance 70...
Page 84: ...Technical data 84...
Page 90: ...Mains filters 90...
Page 96: ...Dimension drawings 96 Frame size A...
Page 97: ...Dimension drawings 97...
Page 98: ...Dimension drawings 98 Frame size B...
Page 99: ...Dimension drawings 99...
Page 100: ...Dimension drawings 100 Frame size C air cooled module...
Page 101: ...Dimension drawings 101...
Page 102: ...Dimension drawings 102 Frame size C for cold plate mounting...
Page 103: ...Dimension drawings 103 Frame size D air cooled module...
Page 104: ...Dimension drawings 104 Frame size D for cold plate mounting...
Page 106: ...Dimension drawings 106 Mains filters type JFI xx...
Page 108: ...Dimension drawings 108 Braking resistors type JBR xx...
Page 110: ...Dimension drawings 110...
Page 111: ......