Parameters 319
Defines the minimum limit for the process PID controller
output. Using the minimum and maximum limits, it is possible
to restrict the operation range.
0.0
-32768.0 …
32767.0
Minimum limit for process PID controller output.
1 = 1
Defines the maximum limit for the process PID controller
output. See parameter
.
1500.0;
1800.0
(
b0)
-32768.0 …
32767.0
Maximum limit for process PID controller output.
1 = 1
Freezes (or defines a source that can be used to freeze) the
output of the process PID controller, keeping the output at the
value it was before freeze was enabled. This feature can be
used when, for example, a sensor providing process feedback
must to be serviced without stopping the process.
1 = Process PID controller output frozen
See also parameter
Not selected
Process PID controller output not frozen.
0
Selected
Process PID controller output frozen.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
Source selection (see
). -
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...