Parameters 163
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
.
0.000 mA or
V
-22.000 … 22.000
mA or V
Minimum value of AI2.
1000 = 1 mA
or V
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
.
20.000 mA or
10.000 V
-22.000 … 22.000
mA or V
Maximum value of AI2.
1000 = 1 mA
or V
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
(Changing the polarity settings of
and
can
effectively invert the analog input.)
0.000
-32768.000 …
32767.000
Real value corresponding to minimum AI2 value.
1 = 1
Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter
See the drawing at parameter
100.000
-32768.000 …
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
13
Configuration of standard analog outputs.
Displays the value of AO1 in mA.
This parameter is read-only.
-
0.000 … 22.000 mA Value of AO1.
1000 = 1 mA
Selects a signal to be connected to analog output AO1.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
Zero
None.
0
Motor speed used
(page
).
1
Output frequency
).
3
Motor current
(page
4
No.
Name/Value
Description
Def
/
FbEq16
AI
in
(
AI
scaled
(
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...