Parameters 159
Defines the minimum value of frequency output 1. See
diagrams at parameter
.
0 Hz
0…16000 Hz
Minimum value of frequency output 1.
1 = 1 Hz
Defines the maximum value of frequency output 1. See
diagrams at parameter
.
16000 Hz
0…16000 Hz
Maximum value of frequency output 1.
1 = 1 Hz
Defines a filtering time for parameters
. The filtering time will only affect the
DIOs that are in input mode.
10.0 ms
0.3 … 100.0 ms
.
10 = 1 ms
12
Configuration of standard analog inputs.
Triggers the analog input tuning function.
Connect the signal to the input and select the appropriate
tuning function.
No action
AI tune is not activated.
0
AI1 min tune
Current analog input AI1 signal value is set as minimum value
of AI1 into parameter
. The value reverts back to
automatically.
1
AI1 max tune
Current analog input AI1 signal value is set as maximum
value of AI1 into parameter
. The value reverts
back to
automatically.
2
AI2 min tune
Current analog input AI2 signal value is set as minimum value
of AI2 into parameter
. The value reverts back to
automatically.
3
AI2 max tune
Current analog input AI2 signal value is set as maximum
value of AI2 into parameter
. The value reverts
back to
automatically.
4
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The supervision applies a margin of 0.5 V or 1.0 mA to the
limits. For example, if the maximum limit for the input is
7.000 V, the maximum limit supervision activates at 7.500 V.
The inputs and the limits to be observed are selected by
parameter
.
Note:
Analog input signal supervision is only active when
• the analog input is set as the source (using the
or
selection) in parameter
,
,
,
,
, and is being used as the active source, or
• supervision is forced using parameter
.
No action
No action taken.
0
Fault
Drive trips on
1
Warning
Drive generates an
warning.
2
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...