![ABB ACS880-604LC Hardware Manual Download Page 50](http://html.mh-extra.com/html/abb/acs880-604lc/acs880-604lc_hardware-manual_3992050.webp)
Checklist
Check the mechanical and electrical installation of the brake chopper before start-up. Go
over the checklist together with another person.
WARNING!
Only qualified electricians are allowed to carry out the work described below. Obey
the complete safety instructions for the drive. If you ignore the safety instructions,
physical injury or death can occur.
Open the main switch-disconnector of the drive and lock it to open position.
Ensure by measuring that the drive is not powered.
Check that …
The brake chopper module has been attached properly on an even, vertical and non-flammable
mounting plate.
There is an adequately sized protective earth (ground) conductor between the brake chopper and the
cabinet PE busbar.
All protective earth (ground) conductors have been connected to the appropriate terminals and the
terminals have been tightened (pull the conductors to check). The galvanic connection between the
brake chopper module frame and the cabinet is proper. (Fastening points must be unpainted.)
The supply voltage matches the nominal input voltage of the brake chopper module. Check the type
designation label.
The setting of the voltage selection jumper is correct. See section
Selecting the voltage (page 44)
.
The DC cable has been connected to the appropriate terminals, and the terminals have been tightened.
(Pull on the conductors to check.)
Appropriate DC fuses have been installed.
The resistor cable has been connected to the appropriate terminals, and the terminals have been
tightened. (Pull on the conductors to check.)
The brake resistor cable has been routed away from other cables.
The control cables have been connected to the appropriate terminals, and the terminals have been
tightened. (Pull on the conductors to check.)
There are no tools, foreign objects or dust from drilling inside the brake unit cabinet.
All shrouds and the front panel of the brake chopper module are in place. Cabinet doors have been
closed.
The internal cooling circuit has been filled up with the correct type of coolant. See chapter
The cooling unit is running and the coolant is able to flow freely through the drive system.
50 Installation checklist
Summary of Contents for ACS880-604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 604LC 1 phase brake units as modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 20: ...20 ...
Page 33: ...Overview of kits Mechanical installation 33 10 ...
Page 34: ...Stage 1 Installation of common parts 34 Mechanical installation ...
Page 35: ...Stage 2 Installation of mounting plate Mechanical installation 35 10 ...
Page 36: ...Stage 3 Installation of cooling components 36 Mechanical installation ...
Page 37: ...Stage 4 Installation of brake module and attenuator Mechanical installation 37 10 ...
Page 40: ...40 ...
Page 58: ...58 ...
Page 64: ...64 ...
Page 82: ...82 ...
Page 84: ...Brake chopper module NBRW 669 84 Dimension drawings ...
Page 85: ...Attenuator Dimension drawings 85 ...
Page 86: ...Brake resistor 234 300 1320 Ø 7 345 R R 1270 86 Dimension drawings ...
Page 88: ...88 ...
Page 102: ......