Selecting the brake circuit components
1.
Calculate the maximum power generated by the motor during braking (
P
max
).
2.
Select a suitable brake chopper and brake resistor combination for the application using
the data given under
. This condition must be met:
P
brmax
P
max
!
The
P
brmax
values in the rating table are specified for the reference braking cycle (10
seconds of braking, 50 seconds of rest). If the actual duty cycle does not correspond
to the reference cycle, the maximum allowed braking power
P
br
must be used instead.
See section
Calculating the maximum braking power
.
3.
Check the resistor selection. The energy generated by the motor during a 400-second
period must not exceed the resistor heat dissipation capacity
E
R
.
Note:
If the
E
R
value is not sufficient, it is possible to use a four-resistor assembly in which
two standard resistors are connected in parallel, two in series. The
E
R
value of the
four-resistor assembly is four times the value specified for the standard resistor.
Note:
•
The resistor assembly must be equipped with a thermal switch (all SAFUR resistors
include a thermal switch). Make sure that the switch is properly isolated (over 2.5 kV)
and shrouded against contact.
•
A custom resistor can be selected within the limits imposed by the brake chopper. That
is, the resistance value of the custom resistor is at least equal to the resistance value
of the resistor given in the ratings table. You can calculate the braking power capacity
of the resistor using this equation:
P
max
U
DC
R
----------
2
where:
Maximum power generated by the motor during braking
P
max
Voltage over the resistor during braking:
1.35 · 1.25 · 690 V DC when supply voltage is 525…690 V AC
U
DC
Resistor resistance value (ohm)
R
WARNING!
Never use a brake resistor with a resistance value below the minimum allowed
resistance value specified for that particular drive or brake chopper combination.
The chopper and the drive are not able to handle the overcurrent by the low
resistance.
■
Calculating the maximum braking power
The
P
brmax
value for each standard brake chopper and brake resistor combination is given
in the rating table. The rated value is specified for a reference braking cycle (10 s of braking,
24 Planning the installation
Summary of Contents for ACS880-604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 604LC 1 phase brake units as modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 20: ...20 ...
Page 33: ...Overview of kits Mechanical installation 33 10 ...
Page 34: ...Stage 1 Installation of common parts 34 Mechanical installation ...
Page 35: ...Stage 2 Installation of mounting plate Mechanical installation 35 10 ...
Page 36: ...Stage 3 Installation of cooling components 36 Mechanical installation ...
Page 37: ...Stage 4 Installation of brake module and attenuator Mechanical installation 37 10 ...
Page 40: ...40 ...
Page 58: ...58 ...
Page 64: ...64 ...
Page 82: ...82 ...
Page 84: ...Brake chopper module NBRW 669 84 Dimension drawings ...
Page 85: ...Attenuator Dimension drawings 85 ...
Page 86: ...Brake resistor 234 300 1320 Ø 7 345 R R 1270 86 Dimension drawings ...
Page 88: ...88 ...
Page 102: ......