Starting reduced run operation
WARNING!
Obey the safety instructions given in
ACS880 multidrive cabinets and
modules safety instructions
(3AUA0000102301 [English]). If you ignore
the safety instructions, injury or death, or damage to the equipment can
occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
WARNING!
Use the required personal protective equipment. Wear protective gloves and long
sleeves. Some parts have sharp edges.
1. Stop the drive and do the steps in section
Electrical safety precautions (page 46)
before
you start the work.
2. If the control unit is powered from the faulty module, connect the control unit to another
24 V DC power supply. ABB strongly recommends using an external power supply with
supply/rectifier units consisting of parallel-connected modules.
3. Remove the module to be serviced from its bay.
4. Install an air baffle (for example, plexiglass) to the top module guide to block the airflow
through the empty module bay.
5. Switch on the power to the supply/rectifier unit.
6. Enter the number of supply/rectifier modules present into parameter
195.13 Reduced
run mode
.
7. Reset all faults and start the supply/rectifier unit. The maximum current limit is now
automatically set according to the new configuration. A mismatch between the number
of detected modules (parameter
195.14
) and the value set in
195.13
will generate a
fault.
Resuming normal operation
WARNING!
Obey the safety instructions given in
ACS880 multidrive cabinets and
modules safety instructions
(3AUA0000102301 [English]). If you ignore
the safety instructions, injury or death, or damage to the equipment can
occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
1. Stop the drive and do the steps in section
Electrical safety precautions (page 46)
before
you start the work.
2. Remove the air baffle from the module bay.
3. Reinstall the module into its bay.
4. Switch on the power to the supply/rectifier unit.
5. Enter "0" into parameter
195.13 Reduced run mode
.
Maintenance 89
Summary of Contents for ACS880-207
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 207 IGBT supply units Hardware manual ...
Page 2: ......
Page 4: ......
Page 53: ... 3 3 Electrical installation 53 11 ...
Page 54: ...3 54 Electrical installation ...
Page 81: ...4 5 6 7 8 6 10 10 Maintenance 81 ...
Page 94: ...5 6 10 3 4 7 9 8 94 Maintenance ...
Page 99: ... Maintenance 99 ...
Page 100: ... 100 Maintenance ...
Page 103: ...5 6 3 4 8 9 7 Maintenance 103 ...
Page 107: ...5 6 3 4 7 Maintenance 107 ...