10. Replace the module: install the module in reverse order. Mind you fingers. Keep a
constant pressure with one foot on the base of the module to prevent the module from
falling on its back.
Note:
Be careful not to break the fastening screws: tighten the fastening
screws of the module to 22 N·m (16.2 lbf·ft) and fastening bolts of the DC output busbars
to 70 N·m (51.6 lbf·ft).
• Plug the module signal wire set to the module signal connector.
• Fasten the shrouds.
11. Remove the module pull-out ramp and close the cabinet doors.
102 Maintenance
Summary of Contents for ACS880-207
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 207 IGBT supply units Hardware manual ...
Page 2: ......
Page 4: ......
Page 53: ... 3 3 Electrical installation 53 11 ...
Page 54: ...3 54 Electrical installation ...
Page 81: ...4 5 6 7 8 6 10 10 Maintenance 81 ...
Page 94: ...5 6 10 3 4 7 9 8 94 Maintenance ...
Page 99: ... Maintenance 99 ...
Page 100: ... 100 Maintenance ...
Page 103: ...5 6 3 4 8 9 7 Maintenance 103 ...
Page 107: ...5 6 3 4 7 Maintenance 107 ...