5. Run the cables to the appropriate terminals. Wherever possible:
• Use the existing cable trunking in the cabinet.
• Use sleeving wherever the cables are laid against sharp edges.
• Tie the cables to provide strain relief.
• To allow the swing-out frame to open properly, leave some slack in the cable (if the
cable needs to be run to a device in the frame).
6. Cut the cables to suitable length. Strip the cables and conductors.
7. Twist the cable shields into bundles and connect them to the ground terminal nearest
to the terminal block. Keep the unshielded portion of the cables as short as possible.
8. Connect the conductors to appropriate terminals (see the circuit diagrams delivered with
the unit).
9. Fasten the shroud and the swing-out frame.
10. Close the door.
58 Electrical installation