![background image](http://html1.mh-extra.com/html/abb/acs580-01-drives/acs580-01-drives_quick-installation-and-start-up-manual_3438551014.webp)
EN – Quick installation and start-up guide
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
Install optional modules, if any
For installing the optional modules, see the user’s manual.
Check the compatibility with IT (ungrounded) and corner-
grounded TN systems
WARNING!
Do not install the drive with the internal EMC filter connected on an
IT system (an ungrounded power system or a high-resistance-grounded [over
30 ohms] power system) or on a corner-grounded TN system.
If you have an IT (ungrounded) system or a corner-grounded TN system, disconnect
the EMC filter before connecting the drive to the supply network. For information on
how to do it, see the user’s manual.
Install side plates and covers
See figure
on page
1. Reinstall the side plates of the cable entry box. Tighten the retaining screws with a
screwdriver.
2. Slide the cover of the cable entry box on the module from below until the cover
snaps into place.
3. Reinstall the module cover. Tighten the two retaining screws with a screwdriver.
Total load capacity of the Auxiliary voltage 24V (X2:10) is 6.0 W (250 mA / 24 V).
Wire sizes: 0.14…2.5 mm
2
(ter24V, DGND, DCOM, DI, AI, AOO, AGND, RO, STO)
Tightening torques: 0.5…0.6 N·m (0.37...4.43 lbf·ft)