Default I/O connections
Default I/O connections of the ABB Standard macro are shown below.
max.
500 ohm
1…10 kohm
S1
AI1 U/I
Voltage/Current selection for analog input 1
S2
AI2 U/I
Voltage/Current selection for analog input 2
XIA
Signal cable shield and analog input 1
1
SCR
Signal cable shield (screen)
2
AI1
External frequency reference 1: 0(2
)
…10 V
3
AGND
Analog input circuit common
XIB
Reference voltage and analog input 2
4
+10V
Reference voltage 10 V DC
5
AI2
Not used
6
AGND
Analog input circuit common
XIC
Analog outputs
7
AO1
Output frequency:
0…20 mA
8
AO2
Output current:
0…20 mA
9
AGND
Analog output circuit common
S600
AO1 I/U
Voltage/Current selection for analog output 1
X2
Aux. voltage output
10
+24V
Auxiliary voltage 24 V DC
11
DGND
Auxiliary voltage output common
12
DCOM
Digital input common for all
X3A
Programmable digital inputs DI1…DI3
13
DI1
Start/Stop:
Activate to start
14
DI2
Fwd/Rev:
Activate to reverse rotation direction
15
DI3
Constant speed selection
X3B
Programmable digital inputs DI4…DI6
16
DI4
Constant speed selection
17
DI5
Ramp pair selection:
Activate to select 2nd pair
18
DI6
Not used
X6, X7, X8
Relay outputs
19
RO1C
Ready run
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Faulted(-1)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
EIA-485 Modbus RTU
29
B+
Embedded Modbus RTU (EIA-483)
30
A-
31
DGND
S4
TERM
Serial data link termination switch
S5
BIAS
Serial data link bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off. Both circuits must be closed for
the drive to start.
35
OUT2
36
SGND
37
IN1
38
IN2
ABB standard macro: