06 ELECTRICAL INSTALLATION
3BHS799208 E01 REV E
ACS5000 WATER-COOLED
USER MANUAL
102/186
Figure 6-9 Cable entry frame sizes (top) for type 1 sealing modules (bottom)
Table 6-1 Type 1 sealing modules and cables per frame opening
Frame
1
1
2
3
4
5
6A
6B
Location
COU
PCU
PCU
PCU
PCU
EXU
SBU
SBU
Cable entry
top
FS 2/4/6 FS 2/4/6 FS 1/3/5
-
-
√
√
√
Cable entry
bottom
FS 2/4/6
FS 2/4
FS 1/3
FS 6
FS 5
√
√
√
Table 6-2 Maximum number of type 1 sealing modules per frame opening
Frame
1
1
2
3
4
5
6A
6B
RM120
2
2
2
1
1
1
2
1
RM90
-
-
-
-
-
2
2
1
RM60
8
8
8
4
4
6
8
4
Table 6-3 Maximum number of cables per frame opening - 3 core
Frame
1
1
2
3
4
5
6A
6B
∅ 68-99 mm
2
2
2
1
1
1
2
1
∅ 48-71 mm
-
-
-
-
-
2
2
1
Table 6-4 Maximum number of cables per frame opening - single core
Frame
1
1
2
3
4
5
6A
6B
∅ 28-50 mm
8
8
8
4
4
6
8
4
L1 L2
L3
L1 L2
L3
L1
RM120
Frame sizes (FS)
RM60
RM69
A
B
1
2
3
4
5
6
6
Summary of Contents for ACS5000
Page 1: ... SYSTEM DRIVES ACS5000 water cooled User manual 5 36 MVA 6 6 9 kV ...
Page 12: ......
Page 18: ......
Page 186: ......