06 ELECTRICAL INSTALLATION
5.
Remove the cable insulation at the point of entry (Fig. 6-18: 1).
If the outer cable screen is non-conductive, cut open the cable screen
in the middle of the stripped area (Fig. 6-18: 1). To turn the conductive
side inside out, pull the cable screen ends over the cable insulation
(Fig. 6-18: 2). Connect the screens ends with a continuous conducting
foil (Fig. 6-18: 3).
Figure 6-18 Preparing control cables for EMC plates
6.
Pull the cable through the entry plate.
7.
To prevent water from entering the cabinet, fit the grommet tightly
and seal any gaps with silicone.
8.
If you had removed the entry plate, remount it and fasten it properly.
1
2
2
3
3