05 MECHANICAL INSTALLATION
3BHS799208 E01 REV E
ACS5000 WATER-COOLED
USER MANUAL
74/186
5.3
General notes on installation
5.4
Dimensions and clearances
Note:
For information on dimensions, location and size of fixing holes and
clearances, see “Appendix C – Mechanical drawings”.
5.4.1
Rear and top access to the cabinet
Joining the transport units and DC busbars requires rear and top access.
5.4.2
Cabinet roof
The cabinet roof is not designed as a base for foreign devices or cable
ducts. Therefore, do not install any foreign objects on the roof.
5.4.3
Fire protection
To prevent fire from spreading into the drive, apply suitable fire
protection measures.
5.4.4
Cable duct material
Use cable ducts of non-flammable material with non-abrasive surface.
To prevent dust, humidity and animals from entering the drive, protect all
cable entries and exits of cable ducts.
5.4.5
Installation material
Installation material is supplied with the drive in a separate box.
5.4.6
Tools
▲
NOTICE
Risk of component damage,
Observe the following during installation:
• Ensure that no dirt enters the drive.
Always close the doors when work is discontinued and completely
cover openings. Metallic dust in particular may cause failures when
the drive is powered up and cause damage.
• When joining two transport units, do not damage or dislocate the
EMC sealing strip that is glued onto the outer joining surfaces of
the cabinet frame.
• If the transport units are joined but not yet on the base frame, do
not lift and move them with a crane.
Instead, use appropriate transport means, such as heavy load
hydraulics rollers or air cushions.