3BHS799208 E01 REV E
ACS5000 WATER-COOLED
USER MANUAL
143/186
09 CDP CONTROL PANEL
If no key is actuated within one minute (an exception from this is the fault
memory display), the CDP control panel automatically returns to the
actual signals display from other modes.
Actual values
For the complete list of selectable actual signals, see
“Appendix G – Signal and parameter table”.
The actual values are organized in groups.
Fault memory
The fault memory display provides information on the 64 most recent
fault events that occurred in the drive. It displays the name of the fault
and the time it occurred. For instructions on how to display and reset the
fault memory, see “9.2.2.7 Displaying and resetting an active fault”
on page 148.
When the drive generates a fault or alarm, the corresponding message
displays immediately.
Changing from the fault memory display to other modes is possible
without resetting the fault first. If no key is actuated, the fault or alarm
message displays as long as the fault is active.
9.2.2.2
Selecting the actual signals display
To select the actual signals display, press the ACT key.
Group
Description
Group 01
Measured or calculated motor values
Group 02
Measured or calculated drive values
Group 03
Reference values
Group 04
Status signals of S800 I/O system
Group 05
Communication link and MCB status signals
Group 06
Software version, drive and motor nominal values
Group 07
Control words
Group 08
Status words
Group 09
Fault and alarm words
1 L ->
600.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
ACT
PAR
FUNC
DRIVE
LOC
I
0
RESET
REF
ENTER
REM