BUSY
BOOL
FALSE=No operation active, TRUE=Operation active.
PARAM_NUM_OUT DINT
Handled parameter number: 3 numbers = group, 2 numbers =
index; for example, Par 20.06 = 2006.
VALUE_OUT
DINT
Read parameter value.
In the example below, the Instance Data Block of FB500
ABB_DRIVE_CONTROL_FB
is named as
DRIVE1 and an ACS800 with RPBA-01 PROFIBUS module has been used.
Note:
The FB500
ABB_DRIVE_CONTROL_FB
DPV_MODE variable defines the used protocol. You
must set this variable correctly to make FC500 to work.
Figure 47 Example
Note:
Using one instance of this block, you can either read or write a single parameter from or to the
drive. You can use multiple instances of this block for reading or writing multiple parameters.