FC500 ACS_DRIVE_PARA
FC500 is used to read/write extra parameters between the PLC and the drive.
1. Right-click in the next free network and choose
Insert empty box
.
2. Write
FC500
in the block field to create an instance of FC500 (
FC500 ACS_DRIVE_PARA
is
included in the ABB library ABB_DRIVE_LIB).
Figure 104 FC500
3. Connect the FC500 block inputs and outputs. All block inputs and outputs need to be connected.
For more information on block variables and data types, see section
(page
).
In the example below, the Instance Data Block of FB500
ABB_DRIVE_CONTROL_FB
has been
named
ABB_DRIVE_CONTROL_FB_DB
and an ACS355 with FPBA-01 PROFIBUS module has
been used.
Figure 105 Example FC500
Note:
Using one instance of this block, you can either read or write a single parameter from or to
the drive. You can use multiple instances of this block for reading or writing multiple parameters.