ACS800 Minimum required parameter settings for PROFIBUS DP
The minimum required parameter settings based on factory default settings.
Parameter
Description
Setting
Comment
98.02
COMM.
MODULE LINK
FIELDBUS
Activates fieldbus module
98.07
COMM
PROFILE
ABB
DRIVES
Communication profile ABB drives
51.02
NODE
ADDRESS
[PB NODE]
PROFIBUS DP node address of the drive
51.21
DP MODE
[DP MODE] 1 for DPV1, 0 for DPV0
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 51 to 55)
10.01
EXT 1
STRT/STP/DIR
COMM.CW
Fieldbus interface as source for start and stop
11.03
EXT REF1
SELECT
COMM.RE
F
Fieldbus interface as source for speed reference
16.04
FAULT RESET
SEL
COMM.CW
Fieldbus interface as source for fault reset
(11.05)
EXT REF1
MAXIMUM
[Scale max] Max speed/frequency scaling value (used in function
block/visualization input
SPEED_REF_MAX
). Must be
less or equal to drive parameter max speed/frequency.