Technical Data
Input Cable Fuses
The drive is equipped for branch circuit protection per NEC with standard T/L fuses
listed below. The fuses restrict drive damage and prevent damage to adjoining
equipment in case of a short-circuit inside the drive.
Check that the operating time
of the fuse is below 0.5 seconds.
The operating time depends on the fuse type
(T/L), supply network impedance and the cross-sectional area, material and length
of the supply cable. The fuses must be of the “non-time delay” type. See also
“Planning the Electrical Installation: Thermal Overload and Short-Circuit
Protection.”
Note 1:
In multi-cable installations, install only one fuse per phase (not one fuse per
conductor).
Note 2:
Larger fuses must not be used.
Note 3:
Fuses from other manufacturers can be used if they meet the ratings and
specifications.
Note 4
: Circuit breakers must not be used without fuses.
ACS800-PC type
Input
current
Fuse
A
A
V
Manufacturer
Type
UL class
Three-phase supply voltage 440 V, 460 V, or 480 V
-0170-5
191
250
600
Bussmann
JJS-400
T
-0210-5
243
300
600
Bussmann
JJS-400
T
-0270-5
299
500
600
Bussmann
JJS-400
T
-0300-5
336
500
600
Bussmann
JJS-400
T
-0320-5
424
500
600
Bussmann
JJS-600
T
-0400-5
498
600
600
Bussmann
JJS-600
T
-0440-5
543
800
600
Bussmann
JJS-800 T
-0490-5
590
800
600
Bussmann
JJS-800 T
-0550-5
669
800
600
Bussmann
JJS-800 T
-0610-5
702
800
600
Bussmann
JJS-800 T
PDM code: 00096931-G