62
Maintenance
Maintenance
What this Chapter Contains
This chapter contains preventive maintenance instructions.
Safety
WARNING!
Read the "Safety Instructions"
on the first pages of this manual before
performing any maintenance on the equipment. Ignoring the safety instructions can
cause injury or death.
Maintenance Intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Air FIlter Material
Note:
When installing the filter media, the white side must face the outside of the cabinet and the
colored side must face the inside of the cabinet.
Interval
Maintenance
For instruction, see section
Every 3 months
UL Type 12
Checking and Replacing the Air Filters (min)
Cleanliness check
Heatsink
Every year when
stored
Capacitor reforming
Reforming
Every 6 years
UL Type 12 and all -0490-5 through -0610-5
Replacing the Cabinet Fan
Every 6 years
Drive module cooling fan change (frame size R7)
Replacing the Drive Module Fan (R7)
Every 6 years
Drive module cooling fan change (frame size R8)
Replacing the Drive Module Fan (R8)
Every 10 years
Capacitor change
Capacitors
Enclosure Type
Inlet (door)
Outlet (roof)
UL Type 12
3AUA0000006723 (qty 1)
3AUA0000006722 (qty 2)