ACS 600 MultiDrive – Technical Data
A-20
ACS 600 MultiDrive
Input Power
Connection
Voltage (
U
1
):
380/400/415 VAC 3-
phase
±
10 % for 400 VAC units
380/400/415/440/460/480/500 VAC 3-
phase
±
10 % for 500 VAC units
525/550/575/600/660/690 VAC 3-
phase
±
10 % for 690 VAC units
525...830 VAC 3-
phase
±
10 % for 830 VAC units
Short Circuit Capability
(IEC 439-1)
:
The rated short time withstand
current of ACS 600 MultiDrive is given below.
Frequency:
48 to 63 Hz, maximum rate of change 17 %/s
Input Voltage Unbalance:
±
3 % (EN 60204-1)
Power Factor:
Diode and Thyristor Supply Units
(cos
j
1
): 0.97 (fundamental at nominal load)
(cos
j
): 0.93...0.95 (total)
IGBT Supply Units
cos
j
1
= 1.00 (fundamental at nominal load)
l
=
I
1
/
I
rms
·
cos
j
1
> 0.98 (total) , where
l
is power factor,
I
1
is fundamental input current rms value,
I
rms
is total input current rms value.
Motor Connection
Voltage (
U
2
):
0 to
U
1
,
3-phase symmetrical.
Frequency:
0 to 300 Hz with 380 to 415 V,
0 to 120 Hz with 525 to 690 V
Frequency Resolution:
0.01 Hz
Continuous Current:
1.0 ·
I
2N
(normal use)
Short Term Overload Capacity:
see rating tables (valid
when output
frequency is > 10 Hz)
Field Weakening Point:
8 to 300 Hz
Switching Frequency:
2 kHz (average)
Frame Type
I
cw / 1 s
(kA)
I
pk
(kA)
B1, B2
18
38
B3
37
78
B4, B5
50
105
B4, B5 optional
65
137