ACS 600 MultiDrive – Technical Data
ACS 600 MultiDrive
A-39
Table A-1
The EMC filtering of the ACS 600 MultiDrive units is marked in the type
code as follows. 1= EMC cabinet, 2 = EMC Cabinet with EMC Filters.
Use of the ACx 600 in Second Environment without EMC filtering (EN 61800-3: second
environment includes all establishments other than those directly connected to a low-
voltage power supply network which supplies buildings used for domestic purposes.)
Public Low-Voltage
Network
1. The ACS 600 MultiDrive is equipped with EMC filtering (refer to Table A-1).
2. The ACS 600 MultiDrive is installed according to the instructions given in the
Hardware Manual
(EN code 63700118).
3. The motor and control cables used are selected as specified in the
Hardware
Manual
(EN code 63700118).
4. Maximum cable length is 100 metres.
Without considering the EMC requirements, do not use the ACS 600 MultiDrive on a
low voltage public network supplying domestic premises. This kind of use might cause
radio frequency interference.
ACS 600 Type
Type Code
Character no.
EMC Options
No EMC Filter
Selection
ACS 600 MultiDrive
Supply Section
ACA63xxxxxxxxxxxxx...
16
1, 2
0
Drive Section
ACA610xxxxxxxxxxxx...
16
1
0
Low voltage
Equipment
Low voltage
Equipment
Equipment
(victim)
Supply transformer
Medium voltage network
Static screen
Point of measurement
ACx 600
Neighbouring network